66 GOSSEN Mueller & Weigert
Rectangular Limit Transducers (MESSCONTACTER)
for Direct Current or Direct Voltage
Technical Data
Internal Resistance / Voltage Drop / Power Consumption
(Values only apply with zero point at left or at bottom.)
Contact Assignments
Dimensions
Measuring Range
Internal Resistance / Voltage drop / Power
Consumption
10 mA 100 mV
> 10 mA / 6 A 100 mV
1 V 1 M
> 1 V / 50 V 100 k
> 50 V / 600 V 2 k/V
0/4 ... 20 mA 6 ± 30 %
Connection to shunt
Lead resistance 0.06
6 mA ± 20 %
Measured Quantity
+
12–
11+
Auxiliary Voltage DC +
L+
L
AC L
N
L
N
Relay Output Logic Output
Limit Contact 1
Limit Contact 2
The output contacts are shown in the wiring
diagram in the zero current condition.
+ terminals are electrically connected
within the instrument.
Front Dim.
mm
Nominal
Dimensions, mm
Cutout, mm Installation
Depth (t)
Installation
Depth (t)
a
1
x a
2
h
I
1
x I
2
Relay
Output
Logic
Output
96 x 48 96 x 48 5 92
+0.8
x 45
+0.6
146 126
41
42
43
81+
82-
51
53
52
85+
86-
a
1
x a
2
l
1
x l
2
h
t
Type Pfn 96 x 48 M
Moving-Coil Movement, Edgewise Scale,
Narrow Bezel per DIN 43 718, Dull Black
Description
Analog Limit Transducer (MESSCONTACTER) with Moving-Coil Movement for
Direct Current or Direct Voltage
Reference Conditions
Front Dim. in mm 96 x 48
Type Pfn 96 x 48 M
Scale Length in mm 65
Accuracy Class 1.5
Weight in kg, Approx. for AC aux. voltage
for DC aux. voltage
0.5
0.2
Sampling electronic
Relative Switching Speed 1% max. error as related to scale length
Repetition Accuracy 0.1% at nom. aux. voltage and 23 °C
Number of Contact Marks 1 or 2
Min. Contact Mark Clearance 3% of scale length
Output Relay integrated
Output Contact 1 changeover per contact mark
Switching Capacity with Ohmic Load
Max. Switching Voltage 250 V AC / 250 V DC
Max. Switching Current 6 A AC / 6 A DC
Nominal Switching Capacity 500 VA / 50 W
Service Life at Nominal Switching Capacity > 10
6
switching cycles
Max. Switching Time 500 ms
Auxiliary Voltage (U
H
) see Order Information
Power Consumption, AC Auxiliary Voltage 4 VA
Power Consumption, DC Auxiliary Voltage 4.5 W
Safety Regulations per
IEC/EN 61010-1/A2 VDE 0411-1/A1
Safety Class II (total insulation)
Measuring Circuit:
Overvoltage Category CAT III
Fouling Factor 2
Operating Voltage 300 V
Operating Voltage for Voltage Measuring
Ranges >250 V...600 V 600 V
Test Voltage (to housing) 5.55 kV AC
Front Housing-Panel Protection IP 52
Fasteners screw spindle
Display
Scale Graduation Coarse-fine
Pointer Beam pointer with knife-edge for single and double
graduation
Mechanical Design
Housing Material Polycarbonate, self-extinguishing and drip-proof per UL94V-0
Replaceable Glass faceplate and bezel
Terminals Tab connectors, (IP20 protection)
1 ea. 6.3 x 0.8 mm or 2 ea. 2.8 x 0.8 mm
Reference Quantities Reference Condition
Ambient Temperature 23 °C ± 2 ˚C
Position of Use control panel vertical ± 1°