54 GOSSEN Mueller & Weigert
Moving-Coil Movement with Power Converter, 240˚ Scale,
Narrow Bezel per DIN 43718
Front Dimensions 96 x 96 mm
Type LM 96-250
Scale Length 151 mm
Accuracy Class 1.5
Weight (standard model), Max. 0.86 kg
Intrinsic Consumption, Approx.
Current Path 0.2 VA
Voltage Path Order no.: AB1/AB2/AB12/AB5/AB15 3.0 VA
AB11 3.5 VA
AB4/AB14 3.4 VA
AB6 3.9 VA
AB16 4.3 VA
Nominal Insulation Voltage 660 V
Test Voltage 2 kV
Front Housing-Panel Protection IP 52
Fasteners type S screw clamp
Housing Material polycarbonate
Type LM 96-250
Square Panel Meters
for Active or Reactive Power
Technical Data
Description
Analog Panel Meter with Moving-Coil Movement and Integrated Power Converter
for Active or Reactive Power
Depending upon type of system and power, the power converter consists of one,
two or three multipliers. The multipliers function in accordance with the
TDM process (time division multiplier). The output signals from the multipliers are
added and fed to the moving coil mechanism.
Reference Conditions
Notes Concerning the Determination of Measuring Ranges
The upper measuring range value should be a standard value per DIN 43701:
1 − 1.2 − 1.5 − 2 − 2.5 − 3 − 4 − 5 − 6 − 7.5 − 8
and corresponding powers of ten.
The upper measuring range value must lie within a range of 0.6 to 1.2 times apparent
power.
Apparent power S is calculated from the primary values from the current and voltage
transformers:
where U equals phase-to-phase voltage
Display
Scale Graduation Coarse-fine
Pointer Beam pointer with knife-edge
Mechanical Design
Housing Material Polycarbonate, self-extinguishing and drip-proof per UL94V-0
Fasteners Standard: type S screw clamp
alternative:
• Subklew fasteners
Scale Interchangeable scales
➲ Scales may only be replaced under voltage-free conditions!
Replaceable Glass faceplate and bezel
➲ May only be replaced under voltage-free conditions!
Terminals M4 screw terminals with self-lifting terminal clips. Screws can
be turned with cross-head or standard screw drivers.
Terminal Designation per DIN 43807
Contact Protection Hand-safe full cover included
Reference Quantities Reference Condition
Ambient Temperature 23°C ± 2°C
Position of Use control panel vertical ±1°
Frequency 45 Hz ... 65 Hz
50 Hz ±0.1 Hz for order no.: AB11
Current Components 20 ... 120% of rated value
Voltage Components 98 ... 102% of rated value
Warm-Up Time ≥5 min
Other DIN EN 60051
• Single-Phase AC S = U x I
• Three-Phase S = √3 x U x I