DE3
CIRCUIT BREAKERS
01/15
DE3-34
Automatic Switches
J-Frame
Switch
L-Frame
Switch
Automatic molded case switches open instantaneously at a factory preset magnetic trip point, calibrated to protect only
the molded case switch itself, when it is subjected to high fault currents. The trip point is nonadjustable and provides no
overload or low level fault protection.
Molded case switches open when the handle is switched to the OFF position or in response to an auxiliary tripping
device such as a shunt trip.
All molded case switches will accept the same lugs and accessories as equivalent thermal-magnetic circuit breakers,
with the exception of Q-frame switches which do not have electrical accessories available.
Automatic molded case switches are UL Listed per UL 489 and are CSA Certified.
H-Frame, J-Frame, and L-Frame PowerPact™ Automatic Molded Case Switches, 600 Vac
Circuit
Breaker
Poles
Ampere
Rating
G Withstand L Withstand R Withstand
Terminal Wire Range
Cat. No. Trip Point Cat. No. Trip Point Cat. No. T rip Point
H-F rame
J-F rame
2
150 A HGL26000S15a 2250A HLL26000S15 2250 A — — AL150HD 14 AWG–3/0 A WG Al/Cu
175 A JGL26000S17 3125 A JLL26000S17 3125 A — — AL175JD 4–4/0 AWG Al/Cu
250 A JGL26000S25 3125 A JLL26000S25 3125 A — — AL250JD 3/0 AWG–350 kcmil Al/Cu
3
150 A HGL36000S15 2250 A HLL36000S15 2250 A — — AL150HD 14 AWG–3/0 AWG Al/Cu
175 A JGL36000S17 3125 A JLL36000S17 3125 A JRL36000S17 3125 A AL175JD 4–4/0 AWG Al/Cu
250 A JGL36000S25 3125 A JLL36000S25 3125 A JRL36000S25 3125 A AL250JD 3/0 AWG–350 kcmil Al/Cu
L-F rame
3
400 A LGL36000S40X 4800 A LLL36000S40X 4800 A LRL36000S40X 4800 A AL150HD
AL600LS52K3
(2) 2/0 AWG–500 kcmil Al/Cu
600 A LGL36000S60X 6600A LLL36000S60X 6600 A LRL36000S60X 6600 A AL250JD
4
400 A LGL46000S40X 4800 A LLL46000S40X 4800 A LRL46000S40X 4800 A AL150HD
AL600LS52K4
(2) 2/0 AWG–500 kcmil Al/Cu
600 A LGL46000S60X 6600A LLL46000S60X 6600 A LRL46000S60X 6600 A AL250JD
a True 2P device. Others are a 2P in a 3P module.
Q-Frame (240 Vac) PowerPact™ Automatic Molded Case Switches
Circuit
Breaker
Poles
Ampere
Rating
J Withstand
Wire Range
Cat. No. Trip Point
Q-F rameb
2 225 A QBL22000S22 4500 A
4 AWG–300 kcmil
3 225 A QBL32000S22 4500 A
b Withstand rating of 10 kA at 240 Vac.
P-Frame and R-Frame PowerPact™ Automatic Molded Case Switchesd, 600 Vac
Frame P oles
Ampere
Rating
J Withstand K Withstand L Withstand
Terminal Wire Range
Cat. No. Trip Point Cat. No. Trip Point Cat. No. Trip Point
P
2
600 A PJL26000S60 10 kA PKL26000S60 24 kA PLL24000S60c 10 kA
AL800M23K
(3) 3/0 AWG–500 kcmil
Al or
Cu
800 A PJL26000S80 10 kA PKL26000S80 24 kA PLL24000S80c 10 kA
1000 A PJL26000S10 10 kA PKL26000S10 24 kA PLL24000S10c 10 kA
AL1200P25K
(4) 3/0 AWG–500 kcmil
Al or
Cu
1200 A PJL26000S12 10 kA PKL26000S12 24 kA PLL24000S12c 10 kA
3
600 A PJL36000S60 10 kA PKL36000S60 24 kA PLL34000S60c 10 kA
AL800M23K
(3) 3/0 AWG–500 kcmil
Al or
Cu
800 A PJL36000S80 10 kA PKL36000S80 24 kA PLL34000S80c 10 kA
1000 A PJL36000S10 10 kA PKL36000S10 24 kA PLL34000S10c 10 kA
AL1200P25K
(4) 3/0 AWG–500 kcmil
Al or
Cu
1200 A PJL36000S12 10 kA PKL36000S12 24 kA PLL34000S12c 10 kA
R
2
1200 A — — RKF26000S12 57 kA RLF26000S12 48 kA
R-frame circuit breakers can be
b
us-connected
or cable-connected.
For cable connections, RLTB kit or
equivalent bus structure is required.
Kit is included with 3000 A switches.
For all others, see page DE3-44.
1600 A — — RKF26000S16 57 kA RLF26000S16 48 kA
2000 A — — RKF26000S20 57 kA RLF26000S20 48 kA
2500 A — — RKF26000S25 57 kA RLF26000S25 48 kA
3
1200 A — — RKF36000S12 57 kA RLF36000S12 48 kA
1600 A — — RKF36000S16 57 kA RLF36000S16 48 kA
2000 A — — RKF36000S20 57 kA RLF36000S20 48 kA
2500 A
— — RKF36000S25 57 kA RLF36000S25 48 kA
3000 A — — RKF36000S30 57 kA RLF36000S30 48 kA
c P-frame L-interrupting is available in 480 Vac only.
d UL magnetic trip tolerances are -20% / +30% from the nominal values shown.
H-, J-, L- P-, and R-Frame Withstand Ratingse
Voltage
Withstand
G J K L R
240 Vac 65 kA 100 kA 65 kA 125 kA 200 kA
480 Vac 35 kA 65 kA 50 kA
* 100 kA 200 kA
600 Vac 18 kA 25 kA 50 kA
* 50 kA 100 kA
e The withstand rating is the fault current at rated voltage that the molded case switch will withstand without damage when protected by a circuit breaker
with an equal continuous current rating.
* R-Frame withstand rating is 65kA.
Accessories ........................................ P
ageDE3-39
Optional Lugs ....................................... P
ageDE3-42
Dimensions..............................Pages DE3-54 and DE3-55
Enclosures .................................Pages DE3-56
–DE3-58
Class 600 / Refer to Catalogs 0611CT1001, 0612CT0101