Directed Electronics d300.1 Uživatelský manuál Strana 6

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 26
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 5
PSS EVE0105 A-(en) VAC D300 5
PHYSICAL SPECIFICATIONS (common data for all versions)
Mounting
Attachment to linear stroke actuators
- direct, FlowPak/FlowTop . .with mounting kit EBZG - E
- for casting yoke
acc. to IEC 534-6 (NAMUR) . with mounting kit EBZG - H
or -H1
- for pillar yoke
acc. to IEC 534-6 (NAMUR) . with mounting kit EBZG - K
or -K1
Stroke range
with standard feedback lever (EBZG-A ) 8 ... 70 mm
with extended feedback lever (EBZG-B ) 60 .. 120 mm
with extended feedback lever (EBZG-A1) 110 .. 260 mm
Mounting to rotary actuators acc. VDI/VDE 3845 ....
with ISO namur kit. (EBZG - R)
Materials
Housing and covers .......Aluminum (Alloy No. 230)
finished with DD-varnish
All moving parts of
feedback system .........1.4306 / 1.4571 / 1.4104
Mounting kits ..........V4AorAluminum,finished
with DD-varnish
(depending upon version) . . (Alloy No. 230)
Mounting bracket .........Aluminum (Alloy No. 230)
Pneumatic diaphragms ....Silicone (suitable for use
in the colour- and lacquer
industry)
Weight
Double acting-spool valve......approx. 2.0 kg (4.4 lbs)
Pneumatic connection
NAMUR mounting ........3xfemalethreads 1/4-18NPT
or G 1/4 for pipe diameter 6 to
12mm(0.24to0.47in)forair
supply and outputs y1, y2 to
the actuator
Direct mounting ..........Insteadoftheoutputy1,an
air connection on the back
side with O-ring will be used
(closed at NAMUR mounting).
Electrical Connection
Line entry...............1or2cable glands M20 x1.5
(others with Adapter AD-...)
Cable diameter ..........6to12mm(0.24to0.47in)
Screw terminals ..........2terminals for input,
4 terminals for additional
inputs / outputs
Wirecrosssection........0.3to2.5mm
2
(AWG 22-14)
Testsockets ............foroptions and communicator
connection
Ambient conditions
Operating conditions ......acc.toIEC654-1
The device can be operated at a class Dx location
Ambient temperature
Operation
1)
...........-40...8C(-40...176ºF)
Transport and storage . . . -40 ... 80 ºC (-40 ... 176 ºF)
Storage conditions
acc. to IEC 60721-3-1: ...1K5;1B1;1C2;1S3;1M2
Indicators
LCD (visible)
2)
.........-2 5...70ºC(- 13...158ºF)
LEDs................-40...80ºC(-40...17F)
Relative humidity .........<100%
Protection class
acc.toIEC529.........IP65
3)
acc.toNEMA..........Type4X
Electromagnetic compatibility EMC
Operating conditions ......industrialenvironment
Immunity according to
EN 61326 ..............fulfilled
IEC61326..............fulfilled
EN 61000-6-2 ...........fulfilled
Emission according to
EN 61326
Class A and Class B.....fulfilled
EN 61000-6-4 ...........fulfilled
EN 55011 Group 1,
Class A and Class B.....fulfilled
NAMUR recommendation
EMVNE21............fulfilled
SAFETY REQUIREMENTS
CE label
Electromagnetic
compatibility
4)
...........89/336/EWG
Low-voltage regulation .....73/23/EWGnotapplicable
Safety
According to EN 61010-1
(or IEC 1010-1) ..........SafetyclassIII
Overvoltage Category I
Internalfuses............notreplaceable
Externalfuses ...........Limitationofpower supplies
for fire protection must be observed acc. to EN 61010-1,
appendix F (bzw. IEC 1010-1).
1) Details see Certificates of Conformity
2) Below ñ20 Cthe LCD reacts only slowly; above +70Cthe background
becomes dark.
3) Under service as directed
4) With PROFIBUS or FOUNDATION Fieldbus only, if shield of wiring is
grounded on both sides.
Zobrazit stránku 5
1 2 3 4 5 6 7 8 9 10 11 ... 25 26

Komentáře k této Příručce

Žádné komentáře